Leakage Current Clamp Tester with Bluetooth (M-1141XR)
40mmφCT, AC

Features
- Waveform display is possible with connection to a smartphone
- Measurement data is to be accumulated in the server, and it is available for graph and CSV output
- Auto 5-range: AC 30mA / 300mA / 3A / 30A / 300A
- CT inside diameter: φ40mm
- Minimum resolution: 0.01mA
- Maximum value hold / Data hold function available
- Band path filter with center frequency (fo = 55Hz)
- Compliant with EN 61010, CAT-III 1000V / CAT-IV 600V
- With backlight
Technical Specifications
| Measuring function | Line current Leakage current |
| CT inside diameter | φ40mm |
| AC current range | 30mA / 300mA / 3A / 30A / 300A RMS |
| Minimum resolution | 0.01mA |
| Accuracy | AC 30mA / 300mA / 3A / 30A ±1.2%rdg±5dgtAC 300A 0~200A : ±1.2%rdg±5dgt 200~250A : -3.0%rdg±5dgt 250~300A : -5.0%rdg±5dgt23℃±5℃ 80%RH or less (50 / 60Hz) |
| Interface | Bluetooth 4.2 |
| Filter function | Band pass filter fo=55Hz (Automatically starts when the power is turned on) |
| Max memory function | “Max” mark on LCD with maximum value |
| Other function | Over range display, Data hold, Low battery indication, Auto power off |
| Sampling rate | Two times / second |
| Safety standard | EN61010 Installation category IV 600V or category III 1000V |
| Operating circuit voltage | Less than AC500V (Isolated electric wire) |
| Operating temp & humidity Range | 0~50℃ Less than 85%RH (w / o condensation) |
| Power supply | CR2450×1 |
| Dimension / Weight | W61×H206×D35mm Approx.260g |
| Accessories | Carrying case, Instruction manual |