SF6

Infra Red SF6 Analysis

Infra Red SF6 Analysis – Zerowaste®

Description:EMT deploys state-of-the art technology for emission free analysis of SF6 gas with measurement of 11 gas parameters

SF6 gas is used in T&D netowrks due to high dielectric strength (3 times higher than air) and high arc quenching properties. SF6 being a green house gas it is essential to analyse other reactive by-products.

Features

  • Uses advanced infra red absorption technology with electrochemical cell, bringing laboratory standard measurement to the field
  • Auto operation - connect and walk away. Connect to the circuit breaker and the unit automatically samples the SF6 gas, detects when gas is connected (by sensing the inlet gas pressure) and starts the preselected number of cycles automatically, it then pumps the gas back after the analysis
  • Multi analysis operation- - the user can select up to 5 cycles to run on the same sample. In fully automatic mode, the instrument will run the selected number of cycles then pump the gas back at the end. The user will then be able to view and save the results for the number of measurements taken
  • The lightest ‘pump back’ SF6 analyser at only 15Kg/33lbs and housed in a robust IP67 case with wheels, retractable handle and pockets for hoses and spare parts
  • Fully portable, battery operated (minimum 8 hours) even during gas pump back
  • Automatic pump back for sampled gas (user selectable)
  • Automatic sampling of up to 5 sequential measurements
  • Automatic start of measurement upon detection of gas connection (user selectable)
  • Readings are obtained at just 5 minutes per test with the minimum amount of gas used, typically 250cc per measurement cycle
  • Time programmable moisture purge for highest quality H2O measurement
  • Full colour touch screen display with user friendly interface and USB communication
  • Fully compliant, pre set user selectable methods (CIGRE/IEC/ASTM) plus 3 custom methods
  • Datalogging of up to 1000 sample results  Upgradeable with easy addition of more sen
  • Datalogging of up to 1000 sample results
  • Upgradeable with easy addition of more sensors for measurement of up to 11 gas parameters including CF4, HF, CO, H2S and R12
  • Leak detection probe option.

Technical Specifications

Gases Measured and Options Gas Range Repeatability
SF6 Purity 0-100% +/-0.5% FS1
Dewpoint -60 – 20ºC +/-0.5ºC at -30ºC
HF 0-200ppm +/-5% FS1
SO2 Lo 0-150ppm +/-2% FS1
SO2 Hi 0-500ppm +/-2% FS1
CF4 Lo 0-4000ppm +/-2% FS1
CF4 Hi 0-65% +/-1% FS1
CO HS2 0-1000ppm 0-100ppm +/-5% FS1
R12 0-250ppm +/-5% FS1 3% of FS1
AIR 0-50% 1% of FS1
Detection Limit 3 gm/year
Technology NDIR
SF6 Leak Detection
Type TFT
Size 4.3” 16:9 (wide aspect ratio)
Screen
Resolution 480 x 272 dots
Transmission Mode TN/Transmissive/Normally White
Dot Pitch 0.198 x 0.198
Colours 24 bit
Touchscreen Integrated resistive touch panel
Backlight White LED PWM
Luminance 350Cd/m2 (Typ.)
Type Flash EEPROM
Capacity 1000 results
Memory
Operating Time >8 hours
Charger Input 100-240V – 50/60Hz
Battery
Type USB
Class HID
PC
Communications
Connector Mini AB
0.5 to 10 bar (7 to 145 PSI)
Gas PressureBar = 0.5 to 12 Bar
PSI = 7 to 174 PSI
High Pressure
Temperature Range -20 to 40ºC/-4.0 to 104ºF
Operating Environmental ConditionsHumidity 0-95%RH non-condensing
Weight 15kg (33lbs)
Maximum Dimensions L500 x W300 x D470 mm (19.11” x 12” x 18.5”)
Physical SpecificationsWeight 15kg (33lbs)
Maximum Dimensions L500 x W300 x D470 mm (19.11” x 12” x 18.5”)